Утилита для запуска аппликации из RSView32 на переднем плане (AppStart or Shell() in VBA)

Прислал: oldDad

Скачали: 146
Размер: 976.56 Kb
Дата публикации: 25/01/2007
Сообщить о недоступном файле
Когда RSView32 работает под Windows 98, Windows 2000 или Windows XP и даётся команда AppStart или в VBA используется функция Shell(), RSView32 удерживает фокус так, что запускаемая аппликация стартует в фоновом режиме и не получает фокус. Данная утилита коректирует поведение RSView32.

Цитата:

"Solution:
There is a Windows 98/2000 Operating System setting, FOREGROUNDLOCKTIMEOUT, that the OS uses to determine how long (in milliseconds), after user input that another application can become a foreground application.   By default this value is "200000" ms or 200 Seconds in W2K, and 15000 ms in Win98.  The Windows 2000 default behavior is to wait 200 seconds after the last user input, mouse or keyboard, before allowing any application that is started to become the foreground application.   By setting this timeout to a value of zero (0), a launched application can immediately become the foreground application, which is the same behaviour that can be observed in Windows 95 and Windows NT4.0.

To set the FOREGROUNDLOCKTIMEOUT  setting to zero (0):
Extract the application  W2KSETFGNDLOCKTIMEOUT.EXE from below.
Login as Administrator on the system.
Close all other applications.
Run the W2KSETFGNDLOCKTIMEOUT.EXE application.
Write down the existing value. This is the current setting, in case you decide to change it back.
Change the shown value to zero (0) and then click on the "Set Value" button.
Close the application with the X in the top left corner.
Reboot your computer.

This setting change only needs to be done once on the system.

Although we have tested this utility and are confident that it functions correctly, you must also test this utility thoroughly outside of a production environment before applying it in your project.  It is possible that its functionality does not match your requirements.  It is also possible that a defect in the utility may prevent it from being implemented successfully in your project.  Should you encounter a defect in this utility, please notify Rockwell Software technical support so we can take corrective action.

File attached below


This application requires the Microsoft Visual Basic 6 with Service Pack 4 core libraries. If the application does not execute, download the following installation file (from Microsoft) and run it to install these core libraries. 


(File size: 1.0 MB)
File attached below

Note:  Same concepts apply to Windows XP.   Same concepts apply to RSView SE"


          
 

[ Назад | Начало ]

Комментарии
Вы не можете отправить комментарий анонимно, пожалуйста зарегистрируйтесь.


  
RA & VDT GmbH


Облако тэгов
Error RSLogix ControlLogix sound FTView Control Logix MVI56-104S 1734-AENTR Altivar Add-on Instruction MVI46MCM Ethernet PLC-5 SLC-500 1757-SRM Firmware ComactLogixL32E 1756-L75 1756-RM2 Controlnet cable Promass Client Memory 1769-L32E execution minutes seconds Windows Build 00000d5c Unspecified terminate geehrter automatisch keine globalen Fe

Яндекс цитирования

Smart Solutions VDT GmbH | Friedrich-List-Allee 38, D-41844 Wegberg-Wildenrath, Germany
Tel.: +49 2432 933 57 83 | e-Mail: office@vdt-solutions.de
Все товарные знаки и торговые марки являются собственностью их владельцев.
При использовании материалов сайта ссылка на данный сайт обязательна.
Открытие страницы: 0.132 секунды