[quote:5070eb28cc="mak"]System Platform или Intouch Stand Alone? В случае с системной платформой, нужно делать reconnect DA-объекта- это как дополнительная информация, м.б. пригодится.
[quote:5070eb28cc]Problem
You are using RSLinx Single Node or OEM with Wonderware products, and when Wonderware or the PC starts up, you see a message titled,
Operation Not Supported by RSLinx Single Node (OEM)
containing the following text:
Operation Not Supported by RSLinx Single Node (OEM). RSLinx Single Node (OEM)
supports all DDE formats except FastDDE. RSLinx Single Node (OEM) does not
support 3rd party client applications, or more than one DDE/OPC Topic
active at a time.
Environment
RSLinx Single Node
RSLinx OEM
Cause
By default, Wonderware products use the Wonderware proprietary FastDDE communication method to DDE servers such as RSLinx. RSLinx will sense that Wonderware is a FastDDE client, and display the informational window to indicate that it cannot support this type of operation. FastDDE is only supported by RSLinx Professional and Gateway; RSLinx Single Node and OEM do not support FastDDE.
Solution
The Wonderware product will still work with RSLinx Single Node or OEM; it will connect using a standard DDE connection. However, the data transfer will be slower with the standard DDE protocol, since it uses one packet per item, where FastDDE (and Rockwell Automation's similar AdvanceDDE protocol) is an optimized DDE protocol with multiple items per packet.
To get FastDDE support, upgrade to RSLinx Professional or Gateway, which support FastDDE. See AID9344 - RSLinx Version and Features Matrix for more information on features supported by various versions of RSLinx.
Alternately, you could use RSLinx Single Node or OEM with Wonderware's OPCLink I/O server, which would connect to RSLinx Single Node or OEM using OPC.[/quote:5070eb28cc]
Проверяйте настройки DDE- c FastDDE работать не будет, а может вы вообще, в случае Getaway, по OPC данные забирали?
К тому же от SuitLink можно и отказаться.[/quote:5070eb28cc]
Приложение StandAlone. Да, забираю по OPC. В Интаче передача настроена на SuiteLink
|
System Platform или Intouch Stand Alone? В случае с системной платформой, нужно делать reconnect DA-объекта- это как дополнительная информация, м.б. пригодится.
[quote:900cb092b2]Problem
You are using RSLinx Single Node or OEM with Wonderware products, and when Wonderware or the PC starts up, you see a message titled,
Operation Not Supported by RSLinx Single Node (OEM)
containing the following text:
Operation Not Supported by RSLinx Single Node (OEM). RSLinx Single Node (OEM)
supports all DDE formats except FastDDE. RSLinx Single Node (OEM) does not
support 3rd party client applications, or more than one DDE/OPC Topic
active at a time.
Environment
RSLinx Single Node
RSLinx OEM
Cause
By default, Wonderware products use the Wonderware proprietary FastDDE communication method to DDE servers such as RSLinx. RSLinx will sense that Wonderware is a FastDDE client, and display the informational window to indicate that it cannot support this type of operation. FastDDE is only supported by RSLinx Professional and Gateway; RSLinx Single Node and OEM do not support FastDDE.
Solution
The Wonderware product will still work with RSLinx Single Node or OEM; it will connect using a standard DDE connection. However, the data transfer will be slower with the standard DDE protocol, since it uses one packet per item, where FastDDE (and Rockwell Automation's similar AdvanceDDE protocol) is an optimized DDE protocol with multiple items per packet.
To get FastDDE support, upgrade to RSLinx Professional or Gateway, which support FastDDE. See AID9344 - RSLinx Version and Features Matrix for more information on features supported by various versions of RSLinx.
Alternately, you could use RSLinx Single Node or OEM with Wonderware's OPCLink I/O server, which would connect to RSLinx Single Node or OEM using OPC.[/quote:900cb092b2]
Проверяйте настройки DDE- c FastDDE работать не будет, а может вы вообще, в случае Getaway, по OPC данные забирали?
К тому же от SuitLink можно и отказаться.
|
Спасибо за ответ.
С моим процессором (1756-L61) Studio 5000 не подходит. Остается только:
[quote:e80f39fde3]In earlier versions select highest available major revision and compatible keying.[/quote:e80f39fde3]
Добавлю еще одну рекомендацию:
[quote:e80f39fde3]
Access Level: TechConnect
Date Created: 09/08/2014 08:19 AM
Last Updated: 09/08/2014 08:33 AM
Question
The 1756-CN2 and 1756-CN2R series C appears compatible with the Studio 5000 V21, and RSLogix V20 and V19 in the Compatibility table.
Environment
1756-CNB, 1756-CNBR, 1756-CN2 and 1756-CN2R
Answer
The module 1756-CN2/R is compatible with Studio/RSLogix 5000 V16 and later projects. You should set a 1756-CN/R series B with revision 20 and "Compatible keying" or "Disable keying".
[u:e80f39fde3]The module is not compatible with Redundant systems[/u:e80f39fde3].[/quote:e80f39fde3]
На последнюю строчку не стоит обращать внимание, т.к с октября 2014 года в версии FM 20.055_kit4 наконец-то добавлена поддержка этого модуля.
|
[quote:47cc960fa0][b:47cc960fa0]624531 - Where to find AOP for 1756-CN2 and 1756-CN2R series C rev 25.xxx
[/b:47cc960fa0]
Access Level: Everyone
Date Created: 10/09/2014 12:23 PM
Last Updated: 10/10/2014 02:40 PM
Question
Where to find AOP for 1756-CN2 and 1756-CN2R series C rev 25.xxx?
Answer
CN2 and CN2R do not use Add-On Profile, they use classic profiles.
Series C classic profile will be availabe in Studio 5000 [b:47cc960fa0]V24[/b:47cc960fa0] or higher.
In earlier versions select highest available major revision and compatible keying.[/quote:47cc960fa0]
|
Эта утилита обычно находится на диске c Panel Builder32:
[img:5c1433bd2b]http://www.mrplc.com/kb/Image/Image/ce-panelview-firmware-001.jpg[/img:5c1433bd2b]
Файл самго последнего firmware Version 4.41 для Вашей панели [url=http://vdt-solutions.de/files/m55bdh4.fmw]здесь[/url].
Процесс описан в [url=https://rockwellautomation.custhelp.com/app/answers/detail/a_id/25373]kb25373[/url]:
[quote:5c1433bd2b]Upgrading Firmware:
There are two methods to upgrade the terminal firmware:
Flash ATA Card
PanelView Firmware Upgrade Utility
CAUTION: Upgrading the PanelView Terminal's firmware will result in the erasure of the PanelView runtime application. Before upgrading the PanelView Terminal's firmware, be sure to save the application that resides in the PanelView Terminal via the PanelBuilder32 or WinPFT+ Upload functionality or ensure that a copy of the application (*.PVA file) resides on a local hard drive.
Flash ATA Card:
Requirements: Allen-Bradley 2711-NM24 (or equivalent) Flash ATA Card
Insert the Flash ATA Card into the personal computer's PCMCIA slot and copy the firmware file onto the Flash ATA Card.
Insert it into the PanelView terminal memory card slot located on the back of the terminal.
Power up the unit. The terminal will load the firmware and then restart. This may take a few minutes.
When the configuration screen comes up, firmware upload is complete.
Remove the Flash ATA Card.
PanelView Firmware Upgrade Utility:
Deactivate any programs or drivers that are using the serial communications port by:
If using RSLinx, close RSLinx program.
Disable all drivers associated with the communication port that will be used for downloading the firmware to the PanelView Terminal.
If using INTERCHANGE (older version of interface drivers), disable the INTERCHANGE drivers. (reboot the computer (Windows 95) or exiting Windows and performing an "abicstop" at the DOS prompt.)
Connect the PanelView Terminal to your personal computer via one of the following methods:
For: Remote I/O, Data Highway Plus, DF1, ControlNet, DeviceNet, Profibus, or Modbus terminal (2711-xxx1, xxx8, xxx10, xxx12, xxx14, xxx15, xxx16), connect the RS-232, 2711-NC13 cable between the printer/transfer port of the PanelView and Com1 port of the PC.
For: DH-485/RS-232 terminal (2711-xxx5, xxx9), connect the RS-232, 2711-NC13 cable between the RS-232 (DH-485) comm port of the PanelView and the com1 port the PC.
For: DH-485 terminal (2711-xxx2, xxx3), connect the 1747-PIC module and cable between the RS-485(DH-485) comm port of the PanelView and the com1 port of the PC.
Note: The 1747-PIC must be powered by a separate power supply (1747-AIC, 24Vdc / or / 2711-NP1, DH-485 power supply).
Run the PanelView Firmware Upgrade Utility.
Select the appropriate Display, User Input type, and Protocol combination for the PanelView terminal that will be updated.
Press the “Select Alternate Source Location” button and browse to the directory on the hard drive where the firmware file is saved.
Select the file and press OK.
Select the “Serial COM port” destination radio button and the COM port that will be used for the firmware file download to the terminal.
Press the “Download” button.
Reset the PanelView when prompted by cycling power to the PanelView
On power up, the file will be transferred from the PC to the PanelView terminal.
[/quote:5c1433bd2b]
|
To solve the problem please try to apply this patch roll-up from [url=https://rockwellautomation.custhelp.com/app/answers/detail/a_id/466418]KB 466418 - FactoryTalk View - Patch Roll-up for CPR9 SRx[/url].
You can also copy the latest version of the ActiveX control to the SE server and client computer(s) and re-register it (open command prompt and enter: regsvr32 C:\Windows\System32\<file name> )
|
[url=http://www.prosoft-technology.com/content/download/1059/8285/version/8/file/adm_dev_guide.pdf]Страница 101[/url]
|
After conversation project from RSView 3.20 to FactoryTalk SE 6.0 via HMI Backup/Restore utilities
I start to recieve alarm "Different ActiveX control loaded for display XXXXX that when saved" and
"cause:Trend:Never file used".
I think its connect to using Trend ActiveX control with old version (from RSView 3.20) in new project.
All trends works propertly, but i want to fix this problem.
How to resolve a problem?
|
Выбирайте:
http://www.rockwellautomation.com/support/firmware/overview.page
Controllers -> ControlLogix -> 1756-L63 Redundant -> select a series -> select a version -> Downloads.
Там есть две 16-е версии - 16.057Std и 16.081, внимательно читайте Release Notes, какие модули поддерживаются в какой версии.
|
Есть в KB:
https://rockwellautomation.custhelp.com/app/answers/detail/a_id/463180 (нужен техконнект)
Вкратце:
Problem
After hitting the Calibrate button on the module configuration dialog and then proceeding through the warning dialog RSLogix 5000 appears to hang.
Environment
• 1734-IR2E FRN 3.01
• 1734 Point I/O Analog AOP 6.02.2.0
Solution
Using 65882 - How do I determine the version of an Add On Profile in RSLogix 5000 verify that the version of AOP you are using is 6.02.2.0.
If this is the case please upgrade to version 6.03.3.0 or greater of the AOP. This can be found here;
То есть нужно скачать и установить последнюю версию Add-On-Profiles for RSLogix 5000 для ваших модулей.
Чтобы скачать новые версии аддонов нужно зайти сюда:
http://www.rockwellautomation.com/rockwellautomation/support/downloads.page?
Выбрать: Add-On-Profiles for RSLogix 5000
Прямая ссылка (требуется вход для техподдержки)
https://download.rockwellautomation.com/esd/download.aspx?downloadid=addonprofiles
Проверено, помогает.
|