Вход на форум 
В начало e-Mail

Форум

Ресурсы Rockwell

Product Directory

Essential Components

Literature Library

Knowledge Base

Electronic News&Magazines

Блог

Encompass Program

Product Certification

  


Предыдущие результаты



Предыдущие результаты



Предыдущие результаты

 Проблема была в том, что RSLogix5000 у нас был версии 20.03. Ключевое здесь - это .03. Как нам объяснили в Rockwell (Москва) версии пакетов с таким индексом особо защищены и корректно работают, только со своими версиями контроллеров. У нас стоял SoftLogix 20.01. Взяли RSLogix5000 20.00 и всё правильно заработало

 Ну да, там же написано: "overload thermal protection". Читайте в оригинале, не читайте переводы. [quote:46d330a57e][b:46d330a57e]140M[/b:46d330a57e]-C, D and [b:46d330a57e]F [/b:46d330a57e]Frames: The 140M-C, D and F frame Motor Circuit Protectors have one UL/CSA Listing – as Manual Motor Controllers (with optional approvals for Motor Disconnect and Group Installation). In NEC/CEC Group Installations, these devices must be applied per the appropriate rules which require the use of an upstream Branch-Circuit, Short-Circuit Protective Device (BCPD). See the table on page 2-20 for the specific ratings of each Motor Circuit Protector. The 140M-C, D and F Frame Motor Circuit Protectors are also UL/CSA Listed, together with a Bulletin 100C contactor and Bulletin 193 overload relay, as part of our Bulletin 103T and 107T Self-Protected IEC Combination Starters. [b:46d330a57e]These starters are then able to provide all of the necessary NEC/CEC requirements for the protection and control of individual Motor Branch Circuits without additional protective devices[/b:46d330a57e].[/quote:46d330a57e]

 Двигатель 4кВт, примерно 8А 40M-F8E-C10 - Мотор-автомат 6.3-10А 193-ED1DP - Тепловое реле для 100-K, 3.2-16А 100-K12KF10 - Миниконтакторы 100-K, 12А Биметаллические теплухи ставятся в номинал. Автоматы, которые я использую последние лет 10, выбираются х1,5 - х2 в зависимости от условий. Мотор-автоматы дороже, использую редко, опыта мало. Электронные реле перегрузки ещё не использовал, но по докам, выходит, что они, как и биметаллические, тоже моделируют тепловой режим обмоток двигателя, при этом не зависят от тем-ры окр.среды. По идее, если судить по докам, мотор-автомат выбирается по номиналу мощности. Так-же, читая документацию на 40M-... , до конца не уверен, что правильно понял: данные автоматы обеспечивают функции теплового реле/нет? В русской доке: [quote:5f0d4d1f57]􀁹 Защита от короткого замыкания — магнитный расцепитель для стандартных токов отключения (установлено на 13 x Ie) 􀁹 [b:5f0d4d1f57]Защита от перегрузок — класс расцепления 10[/b:5f0d4d1f57] 􀁹 Компенсация температуры окружающей среды 􀁹 Защита от обрыва фазы 􀁹 Сертификация ATEX для типов C и D[/quote:5f0d4d1f57] На сайте Rockwell: [quote:5f0d4d1f57]Our Bulletin 140M Motor Protection Circuit Breakers can provide a disconnecting means for motor branch circuit, branch-circuit and short-circuit magnetic protection, [b:5f0d4d1f57]overload thermal protection[/b:5f0d4d1f57], and manual switching. These devices are rated from 0.1...630 A.[/quote:5f0d4d1f57]

 Автоматы 140M-F8E-C10 на ток до 10А имеют встроенную 13-кратную по отношению к номинальному току термальную защиту от перегрузки, т.е., 130А. Если Вас это устраивает, то ставить внешнее реле защиты от перегрузки не нужно. Если Вас не устраивает 13-кратная защита, то ставьте внешнее реле серии 193-Eччxx, у которого этот уровень настраивается. Кстати, ставить 193-ED1DP, которое настраивается на ток от 3,2 до 16А на 10-амперный автомат - в чем смысл? Я бы, если уж ставить, поставил бы хотя бы трехкратное по току, или 5-кратное. Если нужно.

 На грузоподъёмных механизмах иные приоритеты - там редко спасают двикатели, чаще людей и грузы. Поэтому там практически никогда не ставят ни тепловые реле, ни мотор-автоматы, а используют плавкие вставки. Считается, что лучше лебёдка с двигателем на 2-х фазах более-менее плавно опустит груз на последнем издыхании, нежели сразу отключившись рухнет вниз. Тормоза, они такие тормоза. [quote:8b274f11ee] Ставить/нет дополнительно на пускатель 100-K12KF10 электронное тепловое реле 193-ED1DP?[/quote:8b274f11ee] Не вижу смысла.

 Может быть, эти сообраэжения помогут понять причину: [quote:fcf93e2f17]FAQ #1: what causes a RED battery LED on Softlogix5800 It will help to start with a little background. Under the hood, SoftLogix uses the same software that RSLogix 5000 does to maintain changes made by another workstation. A heartbeat thread in RSLogix 5000 periodically asks the controller if any changes have been logged to the change log. If so, it reads those changes and applies them to the current image. Likewise, in SoftLogix, there is a separate process, the SL5KServer, which has the same thread. The engine communications with its server via IPC and the server communicates to the engine using normal communication protocols via RSLinx. Following download, the SL5KServer opens the image sent to the engine during download and attempts to go online. Similarly, following a power cycle (or pull/redrop), the server opens an ACD, downloads it to the engine, and automatically goes online as part of a normal download. Either way, once the controller has an image to run, the SL5KServer should be online. Every 10 seconds, a thread in the engine asks the server if it is still online. If it is not, then the engine turns the battery LED ON (RED) and sends a command to the server to ask it to try to go online. If the battery LED was not already ON, it also logs a battery fault. If communications are just busy, the LED may go RED and then when the comm thread has more time, it may eventually turn green again. This thread checks every 10 seconds even if persistent storage save is disabled, since a save will still occur at powerdown. Every time interval, the thread referenced above in the engine will also ask the SL5KServer to perform a save. Following this, it should be clear that anything that would cause RSLogix 5000 to go offline will also cause the SL5KServer to go offline (and hence turn the battery LED RED). A few possibilities: Comm thread in engine not responding for 32 seconds. Any RSLinx communication problem (including a crash). Loss of communications with the engine. Loss of correlation. In addition to these possibilities, the following cases will also cause a RED LED: Fatal exception in SL5KServer (including RSLogix 5000 support DLLs). Any serious error that occurs in the save of the archive: hard disk errors, insufficient disk space, etc.[/quote:fcf93e2f17]

 Здравствуйте все! На компьютере, где развёрнут SoftLogix установлено: 1) Windows 7 Prof SP1 64 bit Рус. 2) RSLinx 3.51 Запущен драйвер VirtualBackPlane 3) SoftLogix V20.01 4) DEP settings set it to 'Turn on DEP for essential Windows programs and services only' При первоначальной загрузке программы в SoftLogix загорается красным Battery Fault, что говорит об ошибке "Persistent Storage Fault". Эта ошибка не даёт выгружать программу из SoftLogix и не позваляет стартовать с сохранённой программой. Как с этим побороться, есть свежие идеи? Заранее благодарен, Борис Сандлер

 Вопрос: Допустим, я ставлю 140M-F8E-C10 на 100-K12KF10. 140M-F8E-C10 обеспечивает: branch-circuit and short-circuit magnetic protection [b:1b97fb5868]overload thermal protection[/b:1b97fb5868] manual switching Ставить/нет дополнительно на пускатель 100-K12KF10 электронное тепловое реле 193-ED1DP?

 Всё правильно, Logix CPU Security Tool не работает с контроллерами версии v21. [quote:4c361752a5]For version 20 or later of the application, if the security commands are unavailable, you need to install FactoryTalk Services Platform.[/quote:4c361752a5] См. публикацию [url=http://literature.rockwellautomation.com/idc/groups/literature/documents/pm/1756-pm016_-en-p.pdf]1756-PM016H-EN-P Logix5000 Controllers Security - March 2015 [/url], со стр. 13

 [quote:3c0c9bf275="orshu"]У нас RSView32 версии 7.30[/quote:3c0c9bf275] Так сделайте update на 7.60.



Предыдущие результаты


Ещё результаты



Предыдущие результаты



Предыдущие результаты



Предыдущие результаты



Предыдущие результаты




Выберите страницу:   [ << Предыдущая страница ] 1 2


  
RA & VDT GmbH


Облако тэгов
Modbus Automation ControlLogix MVI56-MCM Allen-Bradley Logix Windows FactoryTalk PanelView VersaView ControlTower GuardLogix Compact Software Studio Designer 100-E 100-D SMC-50 Energy Saver 1756-RMS-SC Spectrum Encompass Level Ethernet Redundancy Stratix

Яндекс цитирования

Smart Solutions VDT GmbH | Friedrich-List-Allee 38, D-41844 Wegberg-Wildenrath, Germany
Tel.: +49 2432 933 57 83 | e-Mail: office@vdt-solutions.de
Все товарные знаки и торговые марки являются собственностью их владельцев.
При использовании материалов сайта ссылка на данный сайт обязательна.
Открытие страницы: 0.148 секунды