Предыдущие результаты
Здравствуйте уважаемый!!!
Вот что написано в KB:
A55863468 - Configuration Screen Utility: Use only if you have set a project to autorun without a shutdown button (Panel View Plus Only)
Problem: If an application has accidentally been set to autorun with no means of exiting the project, it will continue to run that application even on reboot of the terminal.
Solution: The following utility will bring up the RSView ME Configuration screen where the user can set ME to disable the project autorun option.
Steps:
Method
1) Rename the appropriate attached file to autorun.exe and copy the file to a compact flash card. There are two attached files, one for the PanelView Plus 400 and 600 terminals, another for the PanelView Plus 700, 1000, 1250, and 1500 terminals.
2) Insert the compact flash card into the terminal. The program will automatically execute. (The execution of this program is silent. There is no user interface and no indication that the program had run.)
3) Wait 30 seconds.
4) Remove the compact flash card.
5) Reboot the terminal.
6) Re-configure your terminal settings as desired.
Сами файлы есть в KB, их можно скачать
http://rockwellautomation.custhelp.com/cgi-bin/rockwellautomation.cfg/php/enduser/fattach_get.php?p_sid=RYq7eKxi&p_accessibility=0&p_tbl=9&p_id=26037&p_created=1159113146&p_olh=0
Пробуйте, должно помочь.
Желаю удачи!!!
|
Вот есть такие документы:
[url=http://literature.rockwellautomation.com/idc/groups/literature/documents/at/1734-at001_-en-p.pdf]Application Techniques[/url]
[url=http://literature.rockwellautomation.com/idc/groups/literature/documents/um/1734-um007_-en-p.pdf]User Manual[/url]
[url=http://literature.rockwellautomation.com/idc/groups/literature/documents/in/1734-in581_-en-e.pdf]Installation Instructions [/url]
В них, в частности - в User Manual - описано, как с этим модулем работать.
Удачи!
|
Добрый день!
[quote:97fe1fc75d] Допустим, я хочу купить 5 ключей на конкурентную активацию на стационарные рабочие станции и 5 USB-ключей для ноутбуков (командировочный вариант). Мне придется покупать разные пакеты или достаточно одного пакета с конкурентной+5 USB-ключей?
[/quote:97fe1fc75d]
Придётся покупать 5 пакетов.
[quote:97fe1fc75d]Не нашел описания на софты, какие различия в составах пакетов. Где это можно прочитать?
[/quote:97fe1fc75d]
В настоящее время в прайс-листе сoncurrent-активацией есть пока только один пакет: 9324-RLD600EN[b:97fe1fc75d]F[/b:97fe1fc75d], вскоре появятся ещё версии пакетов.
Состав пакета соответствует 9324-RLD600ENE Full Edition, но добавлена concurrent activation.
Почитать о FactoryTalk Activation можно здесь:
http://vdt-automation.de/files/ft_activation_rus.pdf
|
Да, есть версия с конкурентной активацией, например, 9324-RLD600ENF. Она имеет так называемую [u:2f9c1ce8af][url=http://literature.rockwellautomation.com/idc/groups/literature/documents/fa/ft00-fa001_-en-e.pdf]"floating activation"[/url]:[/u:2f9c1ce8af]
[quote:2f9c1ce8af][b:2f9c1ce8af]What is a concurrent activation?[/b:2f9c1ce8af]
A concurrent activation locks the software activation to an activation server computer. The activation server manages a pool of activations and shares them with client computers over a network connection. Client computers must be configured to search for activations on the activation server. An activation file is not required on each client computer. Concurrent activations can be either floating or borrowed. See the next two questions below.
You can use a dongle for the Host ID for concurrent activation. Only the computer with the dongle attached can serve the activations.
[b:2f9c1ce8af]
What is a floating concurrent activation?[/b:2f9c1ce8af]
Floating activations are automatically checked out to a client computer when the client runs software that requires activation. The activations are automatically checked back in to the activation server when the client shuts down the software or loses its network connection. Floating activations require a continuous network connection.[/quote:2f9c1ce8af]
Но в любом случае нужно покупать количество лицензий, равное максимальному количеству одновременно работающих станций. Т.е. если купить 2 лицензии, то из 10 станций одновременно смогут работать 2 любых.
|
Здравствуйте!
Мне кажется, что для работы ControlLogix с входами\выходами контроллера PLC-5 лучше подойдет сеть Remote I\O. Реализовать это можно с помощью модуля 1756-DHRIO.
Почитать о настройке сетей DH+ и Remote I\O между ControlLogix и PLC-5, о самом модуле можно здесь:
http://literature.rockwellautomation.com/idc/groups/literature/documents/um/1756-um514_-en-p.pdf
|
Посмотрите, пожалуйста, публикацию [url=http://literature.rockwellautomation.com/idc/groups/literature/documents/pm/1756-pm001_-en-p.pdf]1756-PM001I-EN-P[/url].
Главу 16 Handle a Major Fault - там есть даже примеры обработки аварийных ситуаций.
|
[quote:40b46e08b1="oldDad"]Процессор новый? Тогда надо просто прошить ему firmware соответствующей версии.
Если RSLogix версии 13, то прошить firmware 13.34
Если RSLogix версии 15, то прошить firmware 15.05:
http://support.rockwellautomation.com/ControlFlash/
Если так ведёт себя процессор, который раньше работал - попытаться прошить, если не получится - значит, процессор неисправен.[/quote:40b46e08b1]
Т.е. наличие или отсутствие батарейки не должно сказываться на эту ошибку?
|
Процессор новый? Тогда надо просто прошить ему firmware соответствующей версии.
Если RSLogix версии 13, то прошить firmware 13.34
Если RSLogix версии 15, то прошить firmware 15.05:
http://support.rockwellautomation.com/ControlFlash/
Если так ведёт себя процессор, который раньше работал - попытаться прошить, если не получится - значит, процессор неисправен.
|
А и в самом деле, если не жалко поделиться с коллегами - выложите сюда, или пришлите, а я выложу в "Файлы".
В RSLogix5000 v16 эта проблема будет решена, можно будет самостоятельно [u:94da0188bd][url=http://literature.rockwellautomation.com/idc/groups/literature/documents/pp/9324-pp004_-en-p.pdf]Add-On инструкции[/url][/u:94da0188bd] и создавать библиотеки.
|
О калибрации этих модулей Вы можете почитать, например, в документе [url=http://literature.rockwellautomation.com/idc/groups/literature/documents/um/1756-um009_-en-p.pdf]1756-um009_-en-p.pdf[/url], глава 11.
|
Предыдущие результаты